Quick Answer
The dc-link voltage ripple estimation under rated switching conditions computes Δv_pp from the input values you provide.
Calculator
ToolFusion Engineering Network
Access thousands of engineering calculators, standards, and design tools. Join the ToolFusion network for comprehensive engineering resources.
Explore ToolFusionResult Interpretation
DC-link voltage ripple estimation under rated switching conditions computes ΔV_pp in V using the defined engineering formula and the input values provided. ΔV_pp is expressed in V. No universal acceptance threshold is defined by this calculator.
Worked Example
default_test
Given:
- pf = 0.98
- c_dc = 0.005
- f_sw = 4000
- p_ac = 2000000
- v_dc = 1500
Expected Result:
- ΔV_pp = 2.1114289190647
Engineering Interpretation:
Under the given input conditions, the calculated result is: ΔV_pp = 2.1114289190647 V.
The actual numerical result is computed by the Runtime engine using the persisted tool definition. The values shown here come from deterministically validated test cases.
Formula / Method
Δv_pp = (p_ac*sqrt(1-pow(pf,2)))/(2*3.141592653589793*f_sw*c_dc*v_dc)ΔV_pp.
Variables
| Symbol | Label | Role | Description |
|---|---|---|---|
| p_ac | p_ac | INPUT | p_ac |
| pf | pf | INPUT | pf |
| f_sw | f_sw | INPUT | f_sw |
| c_dc | c_dc | INPUT | c_dc |
| v_dc | v_dc | INPUT | v_dc |
| ΔV_pp | ΔV_pp | OUTPUT | ΔV_pp |
Calculation Steps
- Enter the p_ac in W.
- Enter the pf in pu.
- Enter the f_sw in Hz.
- Enter the c_dc in F.
- Enter the v_dc in V.
- Read the Δv_pp (V) from the results.
Frequently Asked Questions
What does this calculator calculate?
The DC-link voltage ripple estimation under rated switching conditions estimates ΔV_pp based on the input parameters you provide
Why is p_ac important in this calculation?
p_ac is directly proportional to Δv_pp. When you enter p_ac in W, the calculator uses it in the engineering formula to compute the output
How should I interpret the result Δv_pp?
The calculator outputs Δv_pp in V. The result is computed directly from the input values using the defined engineering formula
What units should I use for the inputs?
Enter each value in the units shown next to the input field: p_ac (W), pf (pu), f_sw (Hz), c_dc (F), v_dc (V). Make sure all inputs use the specified units for consistent results
What assumptions does this calculator use?
This calculator uses automatically validated engineering formulas. Results are approximate and should be validated against site-specific conditions, applicable codes, and professional engineering judgment
Related Tools
Browse More Tools
Explore the full index of engineering calculators on this vertical site.